ASHLEY-EDISON (UK)
Manufacturers of Voltage Stabilisers – Power Conditioners – Constant Voltage Compensators – Variable Transformers
OSES THREE PHASE OPERATOR MANUAL - EN
Issue No: AE/OSES-3P/TP/07/2011
- Page 11 of 37-
4. POSITIONING, VENTILATION & COOLING
Check for sufficient floor loading capacity before installing the Stabiliser.
The Stabiliser is designed to operate within an ambient temperature range of -15
to 50°C - up to an altitude of 1000 metres. When installed in greater ambient
temperatures and / or altitudes, the maximum rating of the machine should be
derated by 2% for each additional °C, up to a max of 60°C, and 2.5% for each
additional 500 metres.
OSES Stabilisers are forced air-cooled and the airflow paths should not be
obstructed.
The temperature of the air entering OSES unit cubicles should not be allowed to
exceed the temperatures stated above.
For further information on cubicle sizing please refer to the Appendix Section 12.2
of this manual - Enclosure Types.